1. Before installation, check that the pneumatic butterfly valve has no missing parts, the model is correct, there is no impurities in the valve body, and there is no blockage in the solenoid valve and silencer
2. Put the valve and cylinder in the closed state.
3. Install the cylinder on the valve, (the installation direction is parallel or perpendicular to the valve body), and then see whether the screw hole is aligned, there will be no big deviation, if there is a slight deviation, turn the cylinder block a little, and then tighten the screw.
4. After installation, debug the pneumatic butterfly valve (under normal circumstances, the air supply pressure is 0.4~0.6MPa), and the solenoid valve must be manually operated to open and close during debugging (manual operation can be effective after the solenoid valve coil is de-energized), and observe the opening and closing of the pneumatic butterfly valve. If it is found that the valve is a little difficult at the beginning of the opening and closing process during the debugging operation, and then it is normal, it is necessary to adjust the cylinder stroke to reduce (adjust the stroke adjustment screws at both ends of the cylinder a little at the same time, and when adjusting, you need to run the valve to the open position, and then turn off and adjust the air source) until the valve opening and closing action is smooth and closed without leakage. It should also be noted that the adjustable silencer can adjust the opening and closing speed of the valve, but it is not too small, otherwise it may cause the valve to not operate.
5. Defa should be kept dry before installation and should not be stored in the open air
6. Check the pipeline before installing the butterfly valve to ensure that there is no foreign matter such as welding slag in the pipeline
7. The manual opening and closing resistance of the butterfly valve body is moderate, and the torque of the butterfly valve matches the torque of the selected actuator.
8. The specifications of the flange used for butterfly valve connection are correct, and the pipe clamping flange and butterfly valve flange are in line with the standards. It is recommended to use a special flange for butterfly valves, and a flat welded flange should not be used.
9. Confirm that the flange welding is correct, and the flange must not be welded again after the butterfly valve is installed, so as not to burn the rubber parts.
10. The installed pipe flange should be centered, and aligned with the butterfly valve put in.
11. Install all flange bolts, and tighten them by hand, confirm that the butterfly valve and the flange have been aligned, and then carefully open and close the butterfly valve to ensure flexible opening and closing.
12. Open the valve completely, use a wrench to tighten the bolt in diagonal order, no washer, do not tighten the bolt too tightly, in order to prevent serious deformation of the valve ring, the opening and closing torque is too large.